MI L-DTL-53133/ 2B
DRAWI NGS
TA 30554-88-812
- Generator Set, Tactical, Quiet, 5 kW, 400 Hz.
(Copies of drawings required by contractors in connection with specific acquisition
functions should be obtained from the US Army Communications-Electronics Command,
ATTN: AMSEL-LC-CCS-G-GB, 10115 Gridley Road, Suite 201, Fort Belvoir, VA 22060-
5849.)
3. REQUI REMENTS
3.1 Requirements. Requirements for acquiring the product described herein shall
consist of this document and MI L-DTL-53133.
3.2 Description. The set shall be in accordance with TA 30554-88-812 and as
specified herein.
3.3 Reliability. The minimum acceptable mean time between failure (MTBF) for the
set shall be 442 hours with a 80 percent lower confidence limit.
3.4 Size and weight. The maximum operating set dimensions with control panel
doors closed and the total operational weight shall not exceed the following:
Parameter
Dimension
1280 mm (50.4 inches)
Length
808 mm (31.8 inches)
Width
920 mm (36.2 inches)
Height
413 kg (911 pounds)
Weight
3.5 Fuel consumption. Fuel consumption, at all loads up to and including rated load,
shall not be more than 2.65 l/ h (0.70 gallons per hour[ GPH] ) when the set is operating
on referee grade diesel fuel conforming to MI L-F-46162.
3.6 Frequency regulation. The governing system shall maintain the frequency within
3 percent of rated frequency for all loads from no load up to and including rated load.
3.7 Frequency short-term stability (30 seconds). At every constant load from no
load to rated load, the system shall maintain frequency within a bandwidth equal to 2
2