MI L-DTL-53133/ 8C
DRAWI NGS
TA 30554-88-815
- Generator Set, Tactical, Quiet, 30 kW, 400 Hz.
(Copies of drawings required by contractors in connection with specific acquisition
functions should be obtained from the US Army Communications-Electronics Command,
ATTN: AMSEL-LC-CCS-G-GB, 10115 Gridley Rd, Ste 201, Fort Belvoir, VA 22060-5849.)
3. REQUI REMENTS
3.1 Requirements. The requirements for acquiring the product described herein shall
consist of this document and MI L-DTL-53133.
3.2 Description. The set shall be in accordance with TA 30554-88-815 and as specified
herein.
3.3 Reliability. The minimum acceptable mean time between failure (MTBF) for the set
shall be 510 hours with a 80 percent lower confidence limit.
3.4 Size and weight. The maximum operating set dimensions with control panel doors
closed and the total operational weight shall not exceed the following:
Parameter
Dimension
2104 mm (79.3 inches)
Length
897 mm (35.3 inches)
Width
1374 mm (54.1 inches)
Height
1367 kg (3015 pounds)
Weight
3.5 Fuel consumption. Fuel consumption, at all loads up to and including rated load,
shall not be more than 11.37 l/ h (3.00 gallons per hour [ GPH] ) when the set is
operating on referee grade diesel fuel conforming to MI L-F-46162.
3.6 Parallel operation. With their governor and voltage regulator paralleling circuits
interconnected, two sets of the same mode and size operated in parallel shall divide load in
accordance with the following as system load (at rated power factor) is varied between zero
and 100 percent (and vice versa) of the combined rating of the connected sets: