MIL-DTL-38195D
Table VII. Schedule of optional tests. 1/
Test
Test
Test Method (MIL-STD-705)
Requirement
Number
Test Paragraph
Paragraph
3.4.1c
711.3c (To include 45 degrees)
Rain
1a
3.4.1d
660.1d
Inclined operation
2a
3.5.4
670.1b
Fuel consumption
3a
701.2d at -25° F (-31.7° C)
3.4.1
Starting and operating (moderate cold
4a
Battery start)
3.5.5
Audio noise
5a
4.6.2
720.1d (at 10,000 feet, 77° F (25° C))
3.4.1
Altitude operation (before reliability)
6a
3.3.2
Endurance
7a
690.1d; 4.6.9
3.3.1
Reliability
8a
695.1a; 4.6.9
720.1d (At 10,000 feet, 77° F (25° C))
3.4.1
Altitude operation (after reliability)
9a
3.7
Mobility
10a
4.6.7
3.4.3.1
Railroad impact
11a
740.5c; 4.6.3
3.4.3.1
Drop (end)
12a
740.3c; 4.6.4
3.6
Air transportability
13a
4.6.6
3.3
Maintainability demonstration
14a
4.6.8
3.4.4
Humidity
15a
711.1d
3.14
Electromagnetic interference
16a
4.6.5
1/
See 4.5.2.
Table VIII. Endurance test. 1/
Step
Time Period
Output of Load
Normal full rated electrical (AC + 0 air)
1 hour
1
Normal full rated electrical output (DC + 0 air)
1 hour
2
Normal full rated pneumatic output (0 electrical)
1 hour
3
75 percent rated electrical output (AC + air)
1 hour
4
75 percent rated electrical output (DC + air)
1 hour
5
60 percent rated electrical output (AC + air)
¾ hour
6
50 percent rated electrical output (AC + air)
¾ hour
7
25 percent rated electrical output (DC + air)
½ hour
8
25 percent rated electrical output (DC + air)
½ hour
9
Alternate periods as follows:
2 ½ hours
10
Electrical overload rating 3.5.1.2a
5 minutes
10a
No load
5 minutes
10b
Electrical overload rating 3.5.1.2b
5 minutes
10c
No load
5 minutes
10d
Electrical overload rating 3.5.1.2c
5 minutes
10e
No load
5 minutes
10f
1/
See 4.6.9.1.
23
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business