MIL-DTL-6162C
4.5.8 Shunt field voltage. The voltage drop across the shunt field shall be measured between E (negative) and
A for long shunt field generators or between A and the negative brush for short shunt field generators.
4.5.9 Brushes (for brush type machines). Unless otherwise specified, all tests shall be performed without
replacement of brushes.
4.5.10 General instrumentation. Provisions shall be made to determine the following:
a.
Terminal voltage
b.
Load current
c.
Equalizing voltage
d.
Generator speed
e.
Cooling inlet air temperature
f.
Field shunt voltage
g.
Field shunt current
h.
Resistance in series with the shunt field
i.
Total pressure of the inlet cooling air
j.
Ambient air temperature
Additional instrumentation required is specified in the individual test, qualification test information, or acceptance
test information.
4.5.11 Air blast. Unless otherwise specified, blast-cooling air within ± 5° C of the ambient temperature shall
be supplied to the machine in the quantity indicated in Figure 6 (see 3.4.6.1). The temperature of the air shall be
determined by means of a suitable temperature-indicating device whose responsive element is located in the cooling
air duct between the air inlet of the machine and the pressure-determining element.
4.6 Test methods.
4.6.1 Examination of product. Each machine, subassembly, and part shall be examined as the Government
Inspector may deem necessary to determine compliance with this specification with respect to material, standard
parts (see 3.3.1), simplification (see 3.4.2), mounting flange (see 3.4.5.4), QAD coupling (see 3.4.5.6),
maintainability (see 3.4.4), shaft deflection (see 3.4.5.9), cooling air screens (see 3.4.10), overhung moment (see
3.4.14), identification of product (see 3.5), installation instructions (see 3.6), safety wire and staking (see 3.8), screw
threads (see 3.9), rating charts (see 3.4.7), electrical connections (see 3.4.5.10), brushes (see 3.4.5.13),
interchangeability (see 3.4.3), rotation marking (see 3.4.15), dimensions (see 3.4.12), weight (see 3.4.13), bonding
(see 3.4.11), and workmanship (see 3.10).
4.6.1.1 Machine characteristics. The machine bonding and the cold resistance of all windings at the stabilized
ambient temperature of the machine shall be measured (see 4.6.2 and 4.6.18.3) and recorded.
4.6.2 Dielectric strength. The machine shall be run at minimum rated speed, rated voltage, and rated load until
temperature stabilization occurs. While the unit is running and with radio noise filters disconnected, the following
voltages shall be applied between windings and between each winding and frame. No sign of insulation breakdown
or arcing shall be in evidence. Following the dielectric test, the machine shall meet the requirements and initial
measurements of paragraphs 4.6.1.1 and 4.6.7.